Electronic High-Resistance Cable Fault Detection Sheath Fault Pre-Location

Ask Latest Price
Video Channel
Brand Name :XZH TEST
Model Number :XHHG521A
Certification :CE
Place of Origin :Xi'an, Shaanxi, China
MOQ :1 unit
Payment Terms :T/T
Supply Ability :2000 units/month
Delivery Time :5-8 work days
Packaging Details :Wooden case
No-load voltage :≥7500V
Short-circuit current :≥100mA
Positioning ratio accuracy :±(0.2%·L±1) meter
Weight :25kg
Working power supply :AC 220V (±10%), 50Hz±1Hz; 8.4V built-in battery.
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Electronic No-Load Voltage 7500V High-Resistance Cable Fault Detection Sheath Fault Pre-Location High-Voltage Bridge

The cable outer sheath fault tester is designed based on the MURRAY bridge principle and can be used to locate the breakdown points of various wires and cables and the defect points that have no breakdown but low insulation resistance values.

The equipment uses an electric voltage regulator and an R-type transformer to form a high-voltage constant current source, and the button operation can increase or decrease the voltage.

The no-load voltage is 7500V, the short-circuit current is 100mA, and a high-sensitivity amplifier and galvanometer are used to indicate balance. It forms a balanced bridge with a proportional potentiometer, and the whole is placed at a high potential.

The measurement cable is a specially designed two-core high-voltage rubber cable. The four-terminal resistance measurement method is used to avoid errors caused by lead resistance.

The entire panel is at low potential. One-touch operation, enter the cable length and automatically calculate the fault distance. The high voltage source and bridge are integrated in a portable protective box. Therefore, the device has high voltage, light weight, easy operation and safe use.



Electronic High-Resistance Cable Fault Detection Sheath Fault Pre-Location


Technical specification

No-load voltage ≥7500V;
Short-circuit current ≥100mA (when adjusting balance, it is recommended to set it at 5~40mA);
Positioning proportion accuracy ±(0.2%·L±1) meters;
Weight 25kg;
Working power supply AC 220V (±10%), 50Hz±1Hz; 8.4V built-in battery.



Packing list

Host(main unit) 1set
High power connection wires 1set
Power cable 1pcs
Output cable(red, black) 1set
Ground wire 1pcs
Charger 1pcs
Fuse(3A) 5pcs